20 SLC 500 Chassis–Based Processors
Publication 1747-2.39
Application Specific Instructions
Communication Instructions
Proportional Integral Derivative Instruction
Instruction Mnemonic
and Name
Execution Times (µs)
Function -
Output Instructions
SLC 5/01 SLC 5/02 SLC 5/03
SLC 5/04
SLC 5/05
BSL Bit Shift Left
BSR Bit Shift Right
144 + 24
per word
89 + 14
per word
50 + 2.30
per word
31.5 + 2.31
per word
On each false–to–true transition, these
instructions load a data bit into a bit array, shift
the pattern of data through the array, and
unload the end bit of data. The BSL shifts data
to the left and the BSR shifts data to the right.
SQO Sequencer Output 225 137 70 44.1
On each false–to–true transition, these
instructions load a data bit into a bit array, shift
the pattern of data through the array, and
unload the end bit of data. The BSL shifts data
to the left and the BSR shifts data to the right.
SQC Sequencer
Compare
225 137 60 33.2
On successive false–to–true transitions, the
SQC moves a step through the programmed
sequencer file, comparing the data through a
mask to a source word or file for equality.
SQL Sequencer Load 135 56 33.2
On successive false–to–true transitions, the
SQL moves a step through the sequencer file,
loading a word of source data into the current
element of the sequencer file.
Instruction Mnemonic
and Name
Execution Times (µs)
Function -
Output Instructions
SLC 5/01 SLC 5/02 SLC 5/03
SLC 5/04
SLC 5/05
MSG Message Read/
Write
180 203 183
This instruction transfers data from one node
to another on the communication network.
When the instruction is enabled, message
transfer is pending. Actual data transfer takes
place at the end of the scan.
SVC Service
Communications
240 240 200
When conditions preceding it in the rung are
true, the SVC instruction interrupts the
program scan to execute the service
communication portion of the operating cycle.
Instruction Mnemonic
and Name
Execution Times (µs)
Function -
Output Instructions
SLC 5/01 SLC 5/02 SLC 5/03
SLC 5/04
SLC 5/05
PID Proportional
Integral Derivative
3600 272 169.82
This instruction is used to control physical
properties such as temperature, pressure,
liquid level, or flow rate of process loops.