Calibrate Your Module 5-17
1794-OE8H Calibration Item Byte Channel-Mask
The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, e.g., 0x03 >
channel
0 and 1 have to be calibrated. Only one channel can be calibrated at a time. If
there are more channels selected within the calibration commands, the I/O
module signals an error.
Table 5.14 1794-OE8H Calibration Item Byte Value Identifier List
Identifier (Decimal) Value Access Rule
0 Offset channel 0 Read/write
……
7 Offset channel 7
8 Gain channel 0
……
15 Gain channel 7
16 Offset current-read-back channel 0
……
23 Offset current-read-back channel 7
24 Gain current-read-back channel 0
……
31 Gain current-read-back channel 7
32 Offset voltage-read-back channel 0
……
39 Offset voltage-read-back channel 7
40 Gain voltage-read-back channel 0 Read/write
……
47 Gain voltage-read-back channel 7
48 Status mask calibration
49 Reserved
50 Calibration day
51 Calibration month
52 Calibration year
53 Checksum over calibration values Read
54…255 Reserved