Allen-Bradley 1794-IE8H User Manual Page 83

  • Download
  • Add to my manuals
  • Print
  • Page
    / 146
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 82
Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module 5-15
Table 5.12 1794-OE8H Interpretation of Calibration Data Structure Content During Read Access (Error Status)
Command Byte Item Byte Data1 Byte Data2 Byte
Status (Binary) Command Bits 0…5 (Decimal)
01 Error 3 The written min scale value of Current was not
accepted/internal read back erroneous
Channel-mask Value
low-byte
Value
high-byte
4 The written min scale value of Voltage was not
accepted/internal read back erroneous
5 The written max scale value of Current was not
accepted/internal read back erroneous
6 The written max scale value of Voltage was not
accepted/internal read back erroneous
7
Reserved
(1)
Reserved
(1)
Reserved
(1)
Reserved
(1)
8 The calibration values are not set to default 0 0 0
9 The specified calibration value is not set to default Value-identifier
10 The specified calibration value is not written Value
low-byte
Value
high-byte
11
Reserved
(2)
Reserved
(2)
Reserved
(2)
Reserved
(2)
12
Reserved
(2)
13
Reserved
(2)
14
Reserved
(2)
15…61 Unknown command is mirrored back 0 0 0
62
The specified setup value is not written
(3)
Setup
value-identifier
Value
low-byte
Value
high-byte
63
The setup data could not be saved to EEPROM
(3)
000
(1)
Do not use. Designated for future use.
(2)
Reserved. Used during manufacture of the product. Do not use.
(3)
Only for internal use. Do not use for calibration purposes.
Page view 82
1 2 ... 78 79 80 81 82 83 84 85 86 87 88 ... 145 146

Comments to this Manuals

No comments